Sensor Types & Temperature Ranges
for Temperature Transmitters and Displays

Close Window

NOTE: By default, these devices are scaled to the limitations of the RTD or thermocouple type selected, though they may be scaled to a user defined span. Example: Type T thermocouple has a calibrated range of (-)300 to 700 Deg F. The transmitter may be scaled to 100 to 500 Deg F upon user request. This means that the device will have a 4mA output at 100 Deg F and a 20mA output at 500 Deg.F The minimum span in any case is 100 units (Deg. F or C)ec


Thermocouple ranges
According to thermocouple range
Types: B, C (W5), E, J, K, N, R, S, and T.

RTD Ranges (3 or 4 wire connection)
Pt100 (IEC60751, a = 0.00385)
-200 to +1000 °C / -328 to +1832 °F

Pt 100 (JIS1604, a = 0.003916)
-200 to +1000 °C / -328 to +1832 °F

Pt 100 (US, a = 0.003902)
-200 to +1000 °C / -328 to +1832 °F

Pt 1000 (IEC60751, a = 0.00385)
-200 to +200 °C / -328 to +392 °F

Ni 100 (DIN 43760)
-60 to +250 °C / -76 to +482 °F

Ni 1000 (DIN 43760)
-100 to +150 °C / -148 to +302 °F